Can Copper & Aluminium Touch? Galvanic Corrosion Explained
Galvanic corrosion (also called contact corrosion or bimetallic corrosion) is one of the most common problems in the electrical industry whenever dissimilar metals — typically copper and aluminum — are brought into direct contact. This article explains why it is dangerous, what consequences it can produce, and how the CUPAL bimetal material solves it.
Have this joint in front of you right now?
Tell us what meets what — a copper lug on an aluminium busbar, a cable on a mast, bar to bar — plus the bolt size and how many you need. We come back with the transition that fits and a price within 24 hours. Washers ship from stock in 2–10 working days; cut-to-size parts take 5–10 working days in production.
Send us the joint, get a quote in 24 hours →What is galvanic corrosion?
Galvanic corrosion is an electrochemical process that occurs when two dissimilar metals are placed in direct contact in the presence of an electrolyte (moisture, humidity, condensate). The electrochemical potential difference between the two metals drives an electric current; the less noble metal (the anode) gradually dissolves — corrodes.
The electrochemical series
To understand galvanic corrosion, it helps to know where the metals sit in the electrochemical series:
| Metal | Potential (V vs SHE) | Character |
|---|---|---|
| Gold (Au) | +1.50 | Noble (cathode) |
| Platinum (Pt) | +1.18 | Noble |
| Silver (Ag) | +0.80 | Noble |
| Copper (Cu) | +0.34 | Noble |
| Hydrogen (H) | 0.00 | Reference |
| Tin (Sn) | –0.14 | Non-noble |
| Aluminum (Al) | –1.66 | Non-noble (anode) |
| Magnesium (Mg) | –2.37 | Non-noble |
The thermodynamic standard-potential difference is close to 2 V, but that is only an upper bound for pure metals in special electrolytes. In practice — on copper and aluminum electrodes covered with passive oxide films installed in equipment — the open-circuit voltage of the Cu/Al galvanic pair typically settles around ~0.5–1 V depending on the state of the passive layer. The driving force is nevertheless permanently present, which is why a direct Cu/Al joint corrodes progressively in the presence of moisture.
Why is the copper-aluminum combination particularly dangerous?
In electrical distribution it is extremely common for copper cable lugs to connect to aluminum busbars. This pairing is dangerous for several reasons:
1. Significant potential difference
As shown above, the thermodynamic potential difference between copper and aluminum is one of the largest among practical metal pairs; even with passive films, a ~0.5–1 V driving force for galvanic corrosion remains.
2. Moisture presence
Switchgear, distribution boards and outdoor installations almost always have moisture present — either as condensate or as humidity in the air. This provides the electrolyte for the galvanic cell.
3. Growth of aluminum-oxide layer
When the aluminum surface corrodes, an aluminum-oxide layer forms — an electrical insulator. This oxide layer increases the joint's contact resistance.
4. Loosening joints
Corrosion products (aluminum oxide) have larger volume than the original metal, which physically loosens bolted joints.
Real-world consequences
Galvanic corrosion at copper-aluminum joints has serious practical consequences:
Rising contact resistance
The oxide layer and corrosion products increase contact resistance. That leads to temperature rise at the joint, which further accelerates corrosion — a self-sustaining cycle.
Overheating and fire risk
Increased contact resistance generates heat. In high-current applications this temperature rise can reach fire-hazard levels. This is not a theoretical risk — many documented fires trace back to inadequate copper-aluminum joints.
Failure and outages
Loosening, corroded joints fail over time: intermittent contact, arcing, eventually a full outage.
Loss of warranty
Inadequate copper-aluminum joints do not meet the joint requirements specified by the equipment approval standards (IEC 61439, IEC 61238), which can void equipment warranty and raise liability questions.
How does CUPAL solve the problem?
CUPAL bimetal sheet contains both copper and aluminum simultaneously — an EN AW-1050A aluminium core cold-roll-bonded to a Cu-ETP copper layer and diffusion-welded together inseparably. The solution addresses the galvanic corrosion problem on several levels:
1. Same metal contacts same metal
A CUPAL washer or transition element sits between the copper and aluminum conductors so that:
- the copper side faces the copper cable lug
- the aluminum side faces the aluminum busbar
The outer faces contact the same metal on both sides — no potential difference, no galvanic corrosion.
2. The transition zone is protected
The copper-aluminum interface lives inside the CUPAL sheet, where the diffusion weld ensures a permanent, hermetic connection. This transition zone never meets moisture, never grows an oxide layer, never starts the galvanic-corrosion process.
3. Low and stable contact resistance
CUPAL joint contact resistance stays low and stable over the equipment's lifetime, because the critical Cu/Al interface lives in a protected environment within the composite and never contacts moisture.
4. Long-term reliability
CUPAL is a proven, decades-validated material (langjährig bewährt). It is successfully used across Europe in energy-distribution systems, switchgear, lightning protection and renewable-energy installations.
Practical applications
CUPAL washers
The simplest and most common application: M6–M20 CUPAL washers placed between copper cable lugs and aluminum busbars. Installation takes minutes and immediately provides a protected, corrosion-free joint.
CUPAL strips
In lightning-protection systems and cable-lug joints, CUPAL strip is wrapped around the connection point to ensure a corrosion-free transition.
CUPAL transition plates
For larger contact areas (busbars, distribution-board rails), CUPAL transition plates provide uniform contact and full corrosion protection — cut to size on request. Which of the three forms belongs in a given joint — and when a crimped bimetal lug or butt-splice replaces all of them — is worked through joint by joint in connecting copper to aluminium.
Prevention or after the fact?
Preventing galvanic corrosion is always cheaper and simpler than repairing it after the fact. A CUPAL washer costs a fraction of replacing a failed joint, refurbishing switchgear, or — worst case — covering damage from a fire.
Equipment and connector standards (DIN 43671 for busbars, IEC 61439 for low-voltage switchgear, IEC 61238 for cable connectors) set requirements on joints between dissimilar metals — contact resistance, temperature rise, long-term stability — that CUPAL transition elements can meet thanks to decades of proven use.
Questions about preventing galvanic corrosion? Request expert advice — we respond within minutes on business days.
A specific case: copper cable to an aluminium mast
The joint that generates the most questions we receive is a copper bonding, earthing or lightning conductor bolted to an aluminium mast — on a sailing yacht, an antenna or telecom mast, or a wind-turbine tower. Salt spray makes it far worse than the same joint inland. Connecting a copper cable to an aluminium mast without galvanic corrosion covers what fails, why a stainless washer only delays it, and which transition to fit.